NH Plus Series 20-120 kVA

Power to build a lasting competitive advantage

The Modulon NH Plus Series UPS offers a hot-swappable modular structure. As a scalable UPS, the series was designed with the future growth of your business in mind, and can easily be upgraded or expanded as needed to accommodate increased requirements for power. Secure protection for your critical applications is assured thanks to the modular architecture of the NH Plus Series, which features six programmable dry contact outputs and two smart slots, plus redundant auxiliary power and control circuits. The series' N+X module and built-in system redundancy maintain a steady, reliable source of energy with a high efficiency level of up to 94%. The hot-swappable feature ensures that the mean time for repair (MTTR) is close to zero, which helps lower the total cost of ownership (TCO) in terms of both capital expense and operating expense. The system's generator is optimized for low harmonic distortion (iTHD<3%), resulting in even greater value for your initial investment.

System redundancy guarantees reliable power with uninterrupted availability, and a modular design means trouble-free maintenance and easy expansions. The Modulon NH Plus Series UPS is an excellent solution for superb UPS protection in mission critical power supply applications.
 

DISCONTINUED :recommended replacement product DPH 20-80/120 kVA.

Product Introduction

Specifications
  1. Model
  2. NHP-20K / NHP-40K / NHP-60K / NHP-80K / NHP-100K / NHP-120K

  3. Power Rating (kVA / kW*)
  4. NHP-20K: 20 kVA / 18 kW
    NHP-40K: 40 kVA / 36 kW
    NHP-60K: 60 kVA / 54 kW
    NHP-80K: 80 kVA / 72 kW
    NHP-100K: 100 kVA / 90 kW
    NHP-120K: 120 kVA / 108 kW

  5. Input
  6. Nominal Voltage: 380/220, 400/230, 415/240 Vac (3 phase, 4-wire + G)
  7. Voltage Range: 300~477 Vac (full load), 208~300 Vac (70~100% load)
  8. Current Harmonic Distortion: < 3% (full load)
  9. Power Factor: > 0.99
  10. Frequency: 45~65 Hz

  11. Output
  12. Voltage: 380/220, 400/230, 415/240 Vac (3 phase, 4-wire + G)
  13. Output Power Factor: 0.9
  14. Voltage Harmonic Distortion: ≤ 3% (linear load)
  15. Voltage Regulation: ± 1% (static)
  16. Frequency: 50/60 ± 0.05 Hz
  17. Overload Capability
    ≤ 125%: 10 minutes; ≤ 150%: 1 minute

  18. Interface
  19. Standard
    RS232 x 1, SMART slot x 2, Output dry contact x 6, Input dry contact x 2, Battery cabinet temperature x 4, Battery cabinet status detection x 1, Parallel port x 1, REPO x 1

  20. Conformance
  21. Safety: CE, RCM
    UPS Classification According to IEC 62040-3: VFI-SS-111

  22. Other Features
  23. Parallel Redundancy
    Module and system redundancy
    Maximum 4 units in parallel up to 480 kVA
  24. Emergency Power Off: Local and remote
  25. SRAM Event Log: 500 records

  26. Efficiency
  27. AC-AC: 94%
  28. ECO Mode: 97%

  29. Environment
  30. Operating Temperature: 0~40ºC
  31. Relative Humidity: 0~95% (non-condensing)
  32. Audible Noise (at one meter)
    NHP-20K: < 65 dB
    NHP-40K: < 68 dB
    NHP-60K: < 68 dB
    NHP-80K: < 70 dB
    NHP-100K: < 72 dB
    NHP-120K: < 73d B
  33. IP Protection: IP20

  34. Physical
  35. Dimensions (W x D x H) - UPS
    NHP-20K~80K: 520 x 910 x 1165 mm
    NHP-100K~120K: 520 x 975 x 1695 mm
  36. Dimensions (W x D x H) - Battery Pack
    NHP-20K~80K: 520 x 855 x 1165 mm (26 Ah x 40 pcs)
    NHP-100K~120K: 520 x 855 x 1695 mm (40 Ah x 40 pcs)
  37. Weight
    NHP-20K: 170 kg
    NHP-40K: 200 kg
    NHP-60K: 230 kg
    NHP-80K: 260 kg
    NHP-100K: 350 kg
    NHP-120K: 380 kg

  38. * Power rating in kW is Subject to reconfiguration of the UPS; Delta provides the configuration service.

    All specifications are subject to change without prior notice.
Download

NH Plus Series 20-120 kVA UPS (Leaflet) / 629 KB

 

NH Plus Series 20-120 kVA UPS (User Manual) / 4.09 MB