Modular UPS: DPH Series, 25 - 75/150/200 kVA

Ultimate Availability Without Compromising Power Efficiency

The Modulon DPH Series UPS is a modular UPS used extensively for critical operations, since it provides 25% more power output compared to power factor 0.8 UPS systems. Designed for the most stringent datacenter requirements, the Modulon DPH Series offers the highest possible availability. With its modular structure, the true on-line, double conversion, three-phase Modulon DPH Series UPS system offers a scalable architecture for optimal power designs. It provides 25kW to 200kW of uninterruptible power with additional 800kW capacity in parallel.

The Modulon DPH Series’ scalable architecture is available in a 19" enclosure, and supports vertical and horizontal expansion for versatile installation arrangements. Integration of your power distribution can take shape within the same rack or in parallel rack enclosures. Optimal placement is ultimately decided by the needs of the datacenter, not the limitations of the UPS system.

Built-in redundancy guarantees a continued power supply for mission critical applications, and the fully fault-tolerant design of the Modulon DPH Series offers self-redundancy for the control mechanism, cooling and power modules. Mean time to repair (MTTR) is close to zero, due to hot-swappable functionality for all critical components. In the event of failure by the main module, full control logic enables the system to self-synchronize and switch to the backup, for a seamless transition with no disruption to operations.

UPS DPH Series - features

Product available regions :
Because product specifications vary slightly from region to region, please download your local leaflet or visit your local website for detailed product information.

EMEA North America South America SEA India China Taiwan South Korea
 


Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

Ultimate Availability
 

The Modulon DPH supports ultimate availability to ensure the continuity of mission critical operations.
 

As illustrated, the Modulon DPH can run under inverter mode and bypass mode to sustain uninterruptible power supply to critical load:

High Scalability
 

Modularity Designed for Scalability

 

High Efficiency
 

Excellent power performance and efficiency directly translate into significant reduction of operational costs.

 

The Modulon DPH demonstrates excellent power performance with low total input harmonic distortion (iTHD < 3%). Its reduced load pollution increases power quality, optimizes generator sizing to increase your investment savings, reduces installation costs, and extends the life of valuable equipment.
 

 

Excellent power performance and efficiency lower operation costs significantly. The Modulon DPH combines these benefits to provide high performance, efficient power protection to maximize operational savings for any datacenter.

 

Easy Maintenance
 

Hot plug and hot swap simplify the maintenance process.

Architecture

Specifications
  1. Model
  2. DPH-75K / DPH-150K / DPH-200K

  3. Power Rating
  4. DPH-75K: 25, 50, 75 kVA/kW
    DPH-150K: 25, 50, 75, 100, 125, 150 kVA/kW
    DPH-200K: 25, 50, 75, 100, 125, 150, 175, 200 kVA/kW

  5. Frame
  6. DPH-75K: 75 kW
    DPH-150K: 150 kW
    DPH-200K: 200 kW

  7. Input
  8. Nominal Voltage: 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire +G)
  9. Voltage Range: 176~276 Vac / 305~477 Vac*
  10. Current Harmonic Distortion: < 3%**
  11. Power Factor: > 0.99
  12. Frequency: 50/60 Hz***

  13. Output
  14. Voltage: 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire +G)
  15. Output Power Factor: 1 (kVA=kW)
  16. Voltage Harmonic Distortion: ≤ 2% (linear load)
  17. Voltage Regulation: ± 1% (static)
  18. Frequency: 50/60 Hz
  19. Frequency Regulation: ± 0.05 Hz
  20. Overload Capacity: ≤ 125%: 10 minutes; ≤ 150%: 1 minute

  21. Interface
  22. Standard:
    System communication port x 1, LCM port x 1, Parallel port x 2, Smart slot x 2, Output dry contact x 6, Input dry contact x 2, Battery dry contact x 2, REPO
  23. Optional:
    SNMP IPv6 card, ModBus card, Relay I/O card, Battery cabinet temperature sensor cable, Battery cabinet status detection kit

  24. Conformance
  25. Safety & EMC: BSMI, CE, EN62040-1

  26. Other Features
  27. Parallel Redundancy and Expansion: Module and system redundancy; Maximum 4 units
  28. Emergency Power Off: Local and remote
  29. Battery start: Yes
  30. Event Log: 3000 records

  31. Efficiency
  32. AC-AC: 96% (Tested by TÜV)
  33. ECO Mode: 99%

  34. Environment
  35. Operating Temperature: 0~40˚C
  36. Relative Humidity: 0~95% (non-condensing)
  37. Audible Noise (at one meter): < 62 dBA

  38. Dimensions (WxDxH): 600 x 1090 x 2000 mm

  39. Weight
  40. UPS System
    DPH-75K: 310 kg
    DPH-150K: 320 kg
    DPH-200K: 350 kg
  41. Power Module: 32 kg
  42. Rack-mount PDC
    DPH-75K: 32 kg
    DPH-150K: 32 kg
    DPH-200K: N/A
  43. Battery Module
    DPH-75K: 29.5 kg
    DPH-150K: N/A
    DPH-200K: N/A

  44. System Frame
  45. 25 kW Power Module
    DPH-75K: 3
    DPH-150K: 6
    DPH-200K: 8

  46. Maximum Capacity
  47. Rack-mount PDC
    DPH-75K: 1
    DPH-150K: 2
    DPH-200K: N/A
  48. Breaker Module (for Rack-mount PDC)
    DPH-75K: 6
    DPH-150K: 12
    DPH-200K: N/A
  49. Battery Module
    DPH-75K: 4
    DPH-150K: N/A
    DPH-200K: N/A

  50. * Lower range 140/242~176/305 Vac is acceptable under 60~100% loading condition.
    ** When input vTHD is less than 1%.
    *** Input frequency range can be adjusted up to 40 Hz to 70 Hz. Delta provides configuration service.

    All specifications are subject to change without prior notice.
Download

DPH Series 25 - 75/150/200 kVA UPS (Leaflet) / 486 KB
for all available regions (English)

 

DPH Series 25-200 kVA UPS (Brochure) / 1.83 MB

 

DPH Series 25-75 kVA UPS (User Manual) / 14.2 MB

 

DPH Series 25-150 kVA UPS (User Manual) / 5.98 MB

 

DPH Series 25-200 kVA UPS (User Manual) / 7.00 MB

 

Rack-Mount Remote Power Panel for DPH Series 75/150 kVA UPS (User Manaul) / 4.42 MB

 


Request a Quote Subscribe Newsletter