HPH Series 20-120 kVA

Best-in-class power protection with maximum power and cost efficiency

Behind every great design there is an answer. Delta's true online double-conversion Ultron HPH Series is the solution for small and medium data centers and mission critical applications requiring highly reliable power protection and unbeatable energy efficiency.

The innovation behind the Ultron HPH Series UPS design incorporates low iTHD (< 3%), 96% AC-AC and 99% ECO mode energy efficiency for increased Total Cost of Ownership (TCO) savings. Fully rated power (kVa=kW) without de-rating, the Ultron UPS offers leading AC-AC efficiency without sacrificing any available power requirements. Increased availability is further augmented through Ultron HPH watch-dog design.

Quite simply, the HPH Series UPS from Delta is a best-in-class (three phase 20/30/40/60/80/100/120 kVA UPS) power protection system that combines maximum available power, unsurpassed energy efficiency, and superior power performance with a significant advantage: TCO savings. HPH is an ideal choice for datacenters as well as for industries involved in factory equipment, communication systems, computer network systems, medical systems, monitoring systems and more. Since the Ultron HPH series UPS was launched in 2013, it has obtained wide adoption by customers and professional organizations worldwide, such as HPH 20 kVA and 30 kVA UPS for the luxury car manufacturers in Germany, key telecommunication operators in Asia, and international medical equipment providers in India, to name a few.

Swappable interior architecture for quick and easy maintenance; Redundant fan design enhances system reliability


Product available regions :
Because product specifications vary slightly from region to region, please download your local leaflet or visit your local website for detailed product information.

EMEA North America South America SEA India China Taiwan South Korea

(20-60 kVA, 208/120 V)

(20-40 kVA)


Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

Best-in-Class Power Performance and Efficiency

  • Fully rated power (kVA=kW) for maximum power availability
  • Leading AC-AC efficiency up to 96% saves energy costs
  • Low harmonic pollution (iTHD < 3%) and high input power factor (> 0.99) reduce upstream investment costs
 

Assured Reliability

  • Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life
  • DSP based technology enables reduction in the number of electronic components to lower failure rate
  • Redundant auxiliary power and fan design* enhance system reliability
    (* Applied for models HPH-60/80/100/120K)
  • Watch-dog design of dual auxiliary power circuit to eliminate single-point failure to ensure reliability
  • Built-in manual bypass ensures continuous power to the load even if the UPS is under maintenance
 

Greater Flexibility

  • A wide choice of configurations, such as N+X redundancy and hot stand-by
  • Adjustable charging current and charging voltage meet different battery configuration requirements
  • Flexible battery configuration optimizes battery investment
 

Superior Serviceability and Management

  • Front-door battery replacement with hot-swappable battery tray design supports easy and quick replacement without turning the unit off (HPH-B / BN)
    HPH-B: UPS integrated battery model has batteries inside
    HPH-BN: UPS integrated battery model has no batteries inside
  • Swappable interior architecture and front access servicing enables quick and easy maintenance
    (Applied for models HPH-60/80/100/120K)
  • Multi-connectivity interface supports remote UPS monitoring and management
Applications

Specifications
  1. Model
  2. UPS:
    HPH-20K / HPH-30K / HPH-40K
    HPH-60K / HPH-80K / HPH-100K / HPH-120K
  3. UPS integrated battery model - batteries inside:
    HPH-20K-B / HPH-30K-B / HPH-40K-B
  4. UPS integrated battery model - no batteries inside:
    HPH-20K-BN / HPH-30K-BN / HPH-40K-BN

  5. Power Rating
  6. HPH-20K: 20 kVA / 20 kW
    HPH-30K: 30 kVA / 30 kW
    HPH-40K: 40 kVA / 40 kW
    HPH-60K: 60 kVA / 60 kW
    HPH-80K: 80 kVA / 80 kW
    HPH-100K: 100 kVA / 100 kW
    HPH-120K: 120 kVA / 120 kW

  7. Input
  8. Nominal Voltage : 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire + G)
  9. Voltage Range
    HPH-20K/30K/40K:
    300~477 Vac (full load), 228~300 Vac (70~100% load)
    HPH-60K/80K/100K/120K:
    332~477 Vac (full load), 228~332 Vac (63~100% load)
  10. Frequency: 40~70 Hz
  11. Power Factor: > 0.99 (full load)
  12. Current Harmonic Distortion: < 3%

  13. Output
  14. Voltage: 380/220 Vac, 400/230 Vac, 415/240 Vac (3 phase, 4-wire + G)
  15. Voltage Regulation: ± 1%
  16. Voltage Harmonic Distortion
    HPH-20K/30K/40K: < 1.5% (linear load)
    HPH-60K/80K/100K/120K: < 2% (linear load)
  17. Overload Capability
    ≤ 105%: continuous
    106~≤ 125%: 10 minutes
    126~≤ 150%: 1 minute
    > 150%: 1 second
  18. Output Power Factor: 1
    Frequency: 50/60 Hz ± 0.05 Hz

  19. Battery
  20. Battery Voltage: 240 Vdc
  21. Type: Support SMF/VRLA/Tubular/Ni-Cd
  22. Quantity
    HPH-20K/30K/40K: 32~50 pcs
    HPH-60K/80K/100K/120K: 32~46 pcs ***
  23. Charge Current (Max.) Built-in
    HPH-20K: 5 A
    HPH-30K/40K: 9 A
    HPH-60K: 10 A
    HPH-80K: 15 A
    HPH-100K/120K: 20 A
  24. Typical Backup Time **
    HPH-20K-BN/B: 15 min
    HPH-30K-BN/B: 10 min
    HPH-40K-BN/B: 9.5 min

  25. Communication Interfaces
    SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6, USB Port x 1 *

  26. Conformance
  27. Safety: CE, RCM
  28. UPS Classification According to IEC 62040-3: VFI-SS-111

  29. Other Features
  30. Parallel Redundancy: Up to 4 units
  31. Emergency Power Off: Yes (local and remote)
  32. Maintenance Bypass Switch: Yes

  33. Efficiency
  34. AC-AC
    HPH-20K/30K/40K: Up to 96%
    HPH-60K/80K/100K/120: > 96% (HPH 40-120 kVA efficiency is tested by TÜV)
  35. ECO Mode: Up to 99%

  36. Environment
  37. Operating Temperature: 0~40˚C
  38. Relative Humidity: 5~ 95% (non-condensing)
  39. Audible Noise
    HPH-20K: < 55 dB
    HPH-30K/40K: < 60 dB
    HPH-60K/80K/100K/120K: < 65 dB

  40. Physical
  41. Dimensions (W x D x H)
    HPH-20K/30K/40K: 380 x 800 x 800 mm
    HPH-60K/80K: 520 x 800 x 1175 mm
    HPH-100/120K: 520 x 800 x 1760 mm
  42. Weight
    HPH-20K: 66.5 kg
    HPH-30K: 86.06 kg
    HPH-40K: 86.5 kg
    HPH-60K: 186.5 kg
    HPH-80K: 191 kg
    HPH-100K/120K: 312 kg

  43. Physical (BN/B)
  44. Dimensions (W x D x H): 490 x 830 x 1400 mm
  45. Weight (with batt.)
    HPH-20K-B: 365 kg
    HPH-30K-B/40K-B : 385 kg
  46. Weight (without batt.)
    HPH-20K-BN: 131 kg
    HPH-30K-BN/40K-BN : 162 kg

  47. HPH-B: UPS integrated battery model has batteries inside
    HPH-BN: UPS integrated battery model has no batteries inside

    * Applied for models HPH-60K/80K/100K/120K
    ** At 70% load with internal battery strings.
    *** UPS needs de-rating for battery quantity 32~36 pcs. Please contact authorized Delta personnel.

    All specifications are subject to change without prior notice.
Download

HPH Series 20/30/40/60/80/100/120 kW UPS (Leaflet) / 208 KB
for EMEA, SEA, South America, Korea (English)

 

HPH Series 20/30/40/60/80/100/120 kW UPS (Leaflet) / 429 KB
for China (Simplified Chinese)

 

HPH Series 20/30/40 kW UPS (Leaflet) / 668 KB
for Taiwan (Traditional Chinese)

 

HPH Series 20/30/40/60 kW UPS 208/120V (Leaflet) / 962 KB
for North and South America (English)

 

HPH Series 20/30/40 kW UPS (User Manual) / 4.40 MB

 

HPH Series 20/30/40 kW UPS - integrated battery model (User Manual) / 4.52 MB

 

HPH Series 60/80/100/120 kW UPS (User Manual) / 2.56 MB

 


Request a Quote Subscribe Newsletter