DPH Series, Three Phase UPS, 20 – 80/120 kVA

DPH Series, Three Phase UPS, 20 – 80/120 kVA2020-10-04T17:33:01+00:00

modular UPS systemsThe next generation of modular UPS systems designed for ultimate availability,excellent performance, high efficiency, and ideally suited for medium-sizeddatacenters.
In this IT intensive world with heavy data traffic driven by cloud, 4G/5G and media streaming applications, IT managers are facing the challenges of increasing rack power density and limited data center space. Delta’s innovative modular UPS technologies provide the answer to customers’ demand for ultimate availability, excellent performance, and high efficiency. The brand-new Delta Modulon DPH series UPS 80/120 kVA achieves the industry’s leading power density of 20kW per module in 2U height, offering the smallest footprint and best space utilization. The Modulon DPH Series UPS is the ideal modular power protection for all critical IT application with its’ small package, flexibility and seamless integration.

UPS systems

Specifications

Model
DPH 80 System / DPH 120 System

Power Rating
DPH 80 System
20/40/60/80 kVA
20/40/60/80 kW
Power Module Quantity : Up to 4 units

DPH 120 System
20/40/60/80/100/120 kVA
20/40/60/80/100/120 kW
Power Module Quantity : Up to 6 units

Input
Nominal Voltage : 220/380V, 230/400V, 240/415V (3-phase, 4-wire + G)
Voltage Range : 305~478 Vac (full load)
Current Harmonic Distortion : ≤ 2% *
Power Factor : > 0.99
Frequency Range : 50/60 Hz

Output
Voltage : 220/380V, 230/400V, 240/415V (3-phase, 4-wire + G)
Voltage Harmonic Distortion : ≦ 1% (linear load); ≦ 4% (non-linear load)
Voltage Regulation : ±1% (static)
Frequency : 50/60 Hz
Overload Capability : ≦ 125% : 10 minute; ≦ 150% : 1 minute; >150%: 1 second

Display : 10” color touch screen

Interface
Standard
External battery temperature dry contact x 4, External switch/breaker status dry contact x 4, Output dry contact x 6, Input dry contact x 4, Parallel port x 2, USB Port (Type A x 2; Type B x 1), RS232 Port x 1, Modbus Port x 1, BMS (RJ45) x 1, Ethernet x 1, SNMP Slot x 1, REPO Port x 1

Conformance
Safety : CE (IEC62040-1, IEC62040-2 (C3: standard, C2: optional)

Efficiency
AC-AC Mode : > 96% (Peak efficiency)
ECO Mode : 99%

Battery
Nominal Voltage : ±240 Vdc (default, ±180Vdc~±276Vdc configurable)
Charge Voltage : ±272Vdc (adjustable from 204V to 312V)
Protection of Battery Deep Discharge : Yes

Environment
Operating Temperature : 0 ~ 40℃
Relative Humidity : 95% (non-condensing)
Audible Noise (at one meter) : < 65 dB
IP Protection : IP20

Others
Parallel Redundancy and Expansion : Module and system redundancy, Maximum 8 units
Battery Start : Yes

Physical
Dimensions (W x D x H) : 600 x 850 x 1445 mm
Weight – UPS System (without power modules) : DPH 80 System : 150 kg / DPH 120 System : 162 kg
Weight – 20kW Power Module (optional) : 18 kg

* When input voltage total harmonic distortion input is less than 1%

All specifications are subject to change without prior notice.