HPH Series, Three Phase, 20/30/40/60/80/100/120 kW

HPH Series, Three Phase, 20/30/40/60/80/100/120 kW2020-10-04T17:25:53+00:00

Ultron HPHBest-in-class power protection with maximum power and cost efficiency
The Ultron HPH is a true online double-conversion UPS offering the best-in-class combination of maximum available power, unbeatable energy efficiency and superior power performance for small data centers and other mission critical applications. With fully rated power (kVA=kW), the Ultron HPH provides maximum available power without de-rating the UPS. Thanks to the three level IGBT topology for both PFC (power factor correction) and inverter, the Ultron HPH features up to 96% AC-AC efficiency. Delta’s advanced digital PFC control also contributes low iTHD < 3% and high input power factor > 0.99 resulting in significant TCO (Total Cost of Ownership) savings. Facilitating increased availability and power performance, the Ultron HPH is an ideal solution for protecting your mission critical operations.

Specifications

Model
HPH-20K, HPH-30K, HPH-40K,
HPH-60K, HPH-80K, HPH-100K, HPH-120K
HPH-20K-BN/B, HPH-30K-BN/B, HPH-40K-BN/B

Power Rating
HPH-20K : 20 kVA/kW
HPH-30K : 30 kVA/kW
HPH-40K : 40 kVA/kW
HPH-60K : 60 kVA/kW
HPH-80K : 80 kVA/kW
HPH-100K : 100 kVA/kW
HPH-120K : 120 kVA/kW

Input
Nominal Voltage : 380/220Vac, 400/230Vac, 415/240Vac (3 phase, 4-wire + G)

Voltage Range
HPH-20~40K : 300~477 Vac (full load), 228~300 Vac (70%~100% load)
HPH-60~120K : 332~477 Vac (full load), 228~332 Vac (63%~100% load)

Frequency : 40~70Hz
Power Factor : > 0.99 (full load)
Current Harmonic Distortion : < 3%

Output
Voltage : 380/220Vac, 400/230Vac, 415/240Vac (3 phase, 4-wire + G)
Voltage Regulation : ± 1 %

Voltage Harmonic Distortion
HPH-20~40K : < 1.5% (linear load)
HPH-60~120K : <2% (linear load)

Overload Capability

≤105 %: continuous

106% ~ ≤125%: 10 minutes

126% ~ ≤150%: 1 minute

>150%: 1 second

Output Power Factor : 1
Frequency : 50/60Hz +/- 0.05Hz

Battery
Battery Voltage : 240Vdc
Type : Support SMF/VRLA/Tubular/Ni-Cd
Quantity
HPH-20~40K : 32-50 pcs
HPH-60~120K : 32-46 pcs***
Charge Current (Max.) Built-in
HPH-20K : 5A
HPH-30/40K : 9A
HPH-60K : 10A
HPH-80K : 15A
HPH-100/120K : 20A
Typical Backup Time**
HPH-20K-BN/B : 15 min
HPH-30K-BN/B : 10 min
HPH-40K-BN/B : 9.5 min

Communication Interfaces
SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6, USB Port x 1*

Conformance
Safety : CE, RCM
UPS Classification According to IEC 62040-3 : VFI-SS-111

Other Features
Parallel Redundancy : Up to 4 units
Emergency Power Off : Yes (local and remote)
Maintenance Bypass Switch : Yes

Efficiency
AC-AC
HPH-20~40K : Up to 96%
HPH-60~120K : > 96% (HPH 40-120K efficiency is tested by TÜV)
ECO Mode : Up to 99%

Environment
Operating Temperature : 0 ~ 40˚C
Relative Humidity : 5% ~ 95% (non-condensing)
Audible Noise
HPH-20K : < 55 dB
HPH-30/40K : < 60 dB
HPH-60~120K : < 65 dB

Physical
Dimensions (W x D x H)
HPH-20~40K : 380 x 800 x 800 mm
HPH-60/80K : 520 x 800 x 1175 mm
HPH-100/120K : 520 x 800 x 1760 mm

Weight
HPH-20K : 66.5 Kg
HPH-30K : 86.06 kg
HPH-40K : 86.5 Kg
HPH-60K : 186.5 kg
HPH-80K : 191 kg
HPH-100/120K : 312 kg

Physical (BN/B)
Dimensions (W x D x H)
HPH-20~40K : 490 x 830 x 1400 mm

Weight (with batt.)
HPH-20K-B : 365 kg
HPH-30K/40K-B : 385 kg

Weight (without batt.)
HPH-20K-BN : 131 kg
HPH-30/40K-BN : 162 kg

HPH-B: UPS integrated battery model has batteries inside
HPH-BN: UPS integrated battery model has no batteries inside

* Applied for models HPH-60/80/100/120K
** At 70% load with internal battery strings.
*** UPS needs de-rating for battery quantity 32-36 pcs. Please contact authorized Delta personnel.

All specifications are subject to change without prior notice.