Ultron HPH Series UPS, Three Phase, 160/200 kVA

Ultron HPH Series UPS, Three Phase, 160/200 kVA2020-10-04T17:26:11+00:00

Ultron HPH seriesHighly reliable and efficient backup power for medium enterprise operations
The brand-new Ultron HPH series 160-200kVA is a true online double-conversion UPS offering the best-in-class combination of power performance and efficiency for medium data centers, pan-IT, and other mission critical applications. Thanks to Delta’s R&D expertise and excellent engineering capabilities, the Ultron HPH features up to 96.5% AC-AC efficiency, low iTHD < 3%, and high input power factor > 0.99 resulting in significant total cost of ownership (TCO) savings. Highlights of the highly reliable Ultron HPH series UPS design include key component redundancy and proactive battery health detection. With its combination of superior availability and power performance, the Ultron HPH 160-200kVA is the top choice for power protection of sustainable medium business operations.

Ultron-HPH-series

Specifications

Model
HPH-160K / HPH-200K

Power Rating
HPH-160K : 160kVA* / 150kW
HPH-200K : 200kVA / 200kW

Input
Nominal Voltage : 220/380 Vac, 230/400 Vac , 240/415 Vac (3-phase, 4-wire + G)
Voltage Range : 176 ~ 276Vac (full load)
Current Harmonic Distortion : ≦ 3% **
Frequency : 40 ~ 70 Hz

Output
Voltage : 220/380 Vac; 230/400 Vac; 240/415 Vac (3-phase, 4-wire + G)
Voltage Harmonic Distortion : ≦ 0.5% (linear load)
Frequency : 50/60 Hz
Frequency Regulation : ±0.05 Hz (battery mode)
Overload Capability : ≦ 125% : 10 minutes; ≦ 150% : 1 minute

Display : 10” color touch screen

Interface
Standard
RS232 x 1, Parallel port x 2, USB x 3, RS485 x 1, Relay I/O card slot x 1, REPO x 1, Input dry contact x 4, Output dry contact x 6,
Battery temperature sensor x 4, External switch detection x 4, RJ45 x 1, Ethernet x 1
Optional : Relay I/O card, Battery cabinet temperature sensor cable

Conformance
Safety :CE, RCM
UPS Classification According to IEC 62040-3 : VFI-SS-111

Efficiency
AC-AC Mode : Up to 96.5%
ECO Mode : 99%

Battery
Nominal Voltage : ±240 Vdc
Charge Voltage : ±272 Vdc (adjustable from 204V to 312V)
Battery number configuration : 30 ~ 46pcs (default: 40pcs)

Environment
Operating Altitude : 1000 meters (without derating)
Operating Temperature : 0 ~ 40℃
Audible Noise : <70 dB
Relative Humidity : 0 ~ 95% (non-condensing)

Others
Parallel Redundancy and Expansion : Maximum 8 units
Remote Emergency Power Off : Yes
Battery Start : Yes

Physical
Dimensions (W x D x H) : 600 x 1100 x 1600 mm
Weight : HPH-160K : 339 kg / HPH-200K : 376 kg

* The power rating is adjustable from default 160kVA to 150kVA via touch panel.
** When input vTHD is less than 1%

All specifications are subject to change without prior notice.

Get In Touch

Contact Us

Have a question or need any assistance that should be answered by a professional? Contact us, and let our staff help you.